This
RTU was designed for a Lift Station using 450MHz radio based SCADA and a
backup RACO Alarm Dialer. The RTU and
the Alarm Dialer each have battery backup which provides for redundant path
reporting of critical alarms such as High Wetwell Level and Power Fail. All
of our RTU’s are built with surge protection on every wire entering or
leaving the enclosure. As a result, we
experience less than 1% failure of expensive electronic devices. |
|
RACO Alarm Dialer |
|
Duplex Outlet for Laptop or other accessories. |
|
Keypad for Operator access to station data. |
|
Telephone Line Surge Protector |
|
12 to 24 VDC Voltage converter to allow battery
backup of field devices. |
|
12 VDC Power Supply |
|
120 VAC high speed secondary Surge Protector |
|
UHF DataRadio for communications to Master |
|
ICL Etherlogic RTU supports communication to Master and all logic
programming for control. Supports Digital inputs and outputs and Analog inputs and outputs. Supports Ethernet and Serial communications. |
|
4-20 ma Surge Protection for inputs such as level
transmitters and flow meters. |
|
Relay interface for all Digital inputs and outputs for surge protection
and LED indication of operation. |
|
120 VAC 10 Amp circuit breaker for power control
primary surge protection. |
|
Snap Trac style wire trough to protect wiring and make service easier. |
|
All 120 VAC wiring to duplex outlet, surge unit, and power supply is 14
gage stranded. All other wiring is lower than 30 VDC and is wired with 18 gage stranded.
|